Resources · Energy

Heat rate: what it is, how to calculate it and what degrades it

Heat rate tells you how much fuel energy a power plant needs to deliver one kilowatt-hour. Small changes in this number mean large differences in operating cost.

What heat rate is

Heat rate is the fuel energy a unit consumes for each kilowatt-hour of electricity it generates. The lower it is, the more efficient the unit.

Heat rate = fuel energy ÷ electrical energy generated

It is usually expressed in kJ/kWh, kcal/kWh or BTU/kWh. In kJ/kWh its relationship with efficiency is direct:

Efficiency = 3,600 ÷ heat rate

Two definitions you must always state

  • Gross or net. Net heat rate deducts the plant's auxiliary consumption and reflects the energy actually delivered.
  • Lower heating value (LHV) or higher heating value (HHV). The same test gives different values depending on which is used, so two figures are only comparable if they use the same basis.

A worked example

A simple-cycle gas turbine at ISO conditions receives 773.8 MW of fuel heat (LHV) and delivers 294.2 MW of net electrical power.

Net efficiency
294.2 ÷ 773.8 = 38.0%
Net heat rate
3,600 ÷ 0.3802 = 9,468 kJ/kWh

In this unit, a 1% deterioration in heat rate is equivalent to about 7.7 MW of additional fuel. Over 8,000 operating hours a year that is some 62,000 thermal MWh paid for without generating any more energy.

What degrades it

  • Compressor fouling and pressure drop across the inlet filters.
  • Wear of seals and clearances in turbines and compressors.
  • Condenser fouling and loss of vacuum in steam cycles.
  • Part-load operation and frequent starts and stops.
  • Ambient conditions: air temperature, pressure and humidity.

How to measure it properly

A reliable performance test uses calibrated instrumentation, runs the unit at steady state and corrects the results to reference conditions, so that the effect of the weather is not mistaken for the condition of the machine. The ASME PTC codes are the usual reference for these tests. With a well-established baseline, each later measurement shows how much the unit has degraded and which intervention is worthwhile.

We carry out specific consumption tests and thermal performance analysis in power plants. With Tundra, our simulator, we model the cycle and compare expected performance with measured performance.